Air compressors are one of the most common jobs for a phase converter, and the one people undersize most often. A compressor starts against pressure in the tank, every time it cycles on, all day long. So we size the converter bigger than for a lathe or a saw.
Take the horsepower on the compressor motor nameplate and multiply it by 2.5. Round up to the next converter size. That's the size we recommend for both piston and rotary screw compressors.
Example: a 7.5 HP compressor × 2.5 = 18.75, so you need a 20 HP converter (GP20NL).
| Compressor motor | Math | Converter (NL) | Upgrade with AutoLink (NLA) |
|---|---|---|---|
| 2 HP | 2 × 2.5 = 5 | GP5NL | GP5NLA |
| 3 HP | 3 × 2.5 = 7.5 | GP7NL | GP7NLA |
| 5 HP | 5 × 2.5 = 12.5 | GP15NL | GP15NLA |
| 7.5 HP | 7.5 × 2.5 = 18.75 | GP20NL | GP20NLA |
| 10 HP | 10 × 2.5 = 25 | GP25NL | GP25NLA |
| 15 HP | 15 × 2.5 = 37.5 | GP40NL | GP40NLA |
| 20 HP | 20 × 2.5 = 50 | GP50NL | GP50NLA |
| 25 HP | 25 × 2.5 = 62.5 | GP75NL | GP75NLA |
| 30 HP | 30 × 2.5 = 75 | GP75NL | GP75NLA |
Bigger than 30 HP? Call us. At that size we also check your building's service, because the converter has to be smaller than the kVA of your utility transformer. If your service is limited, a DualZone (two smaller idlers that start one after the other) is usually the answer.
The NL is our standard converter and runs a compressor fine. The NLA adds AutoLink: after a power outage it starts the converter first, then connects the compressor once the converter is up to speed. Nobody has to be there to restart things in the right order, and the compressor never tries to start on a converter that isn't running yet. If your compressor runs unattended, the NLA is worth it.
A compressor cycles on by itself whenever the tank pressure drops, so it can start while your other machines are already running. Size it like this: compressor HP × 2.5, then add the horsepower of every other machine that runs at the same time at 1×.
Example: a 7.5 HP compressor and a 7.5 HP planer: 7.5 × 2.5 + 7.5 = 26.25, so you need a 30 HP converter (GP30NL).
Many compressors can be rewired from 460 V to 230 V; check the nameplate or the wiring diagram on the motor. If it can't be rewired, we have converters with a built-in transformer (NLT) that take 230 V single-phase in and put 460 V three-phase out.
Not sure of the horsepower? Text a photo of the motor nameplate to 800-417-6568, or call the same number and we'll size it with you.
Call 800-417-6568 with your machine list. Every Phoenix converter comes with a lifetime warranty on the control panel; the idler motor carries a 3-year warranty from the motor maker.