Split bolt connector
- Secure mechanical splice connection
- Suitable for properly sized copper conductors
- Tighten to manufacturer specifications
- Insulate connection as required
Complete installation, wiring diagrams, and operating instructions for the Phoenix DualZone Phase Converter family.
⬇ Download DualZone Manual (PDF)Phoenix Precision Balanced · DualZone Series
Single phase to three phase, balanced and built to last — engineered for shops, machinists, and electricians who need a clean three-phase supply from a single-phase service. This DualZone phase converter manual walks the install end to end: mounting, wiring, sizing, startup, and the support handoff if something does not go to plan.
01 — Getting Started
Thank you for choosing a Phoenix Phase Converter. Before installing your unit, review the layout below and the instructions in this manual. Identify all connection points and the wire size chart inside the panel before making any wiring connections.
This manual will guide you through the installation, wiring, and start-up of your DualZone phase converter to ensure safe and reliable operation. The DualZone is a precision-balanced rotary phase converter that turns single-phase utility power into clean three-phase power — a dependable single phase to three phase power source for machine shops, woodshops, farms, and commercial buildings that need to run three-phase equipment from a single-phase service.
Every Dual Zone phase converter ships with the same phase converter control panel layout shown in this guide: a single-phase input on T1/T2, two precision-balanced idler motor outputs, and three-phase L1/L2/L3 terminals for your load.
Read this manual completely before installing or operating the unit. Keep this manual for future reference.
Disconnect and lock out all power sources before installing or servicing this equipment. Failure to follow safety instructions can result in serious injury or equipment damage.
02 — Installation Layer
The phase converter panel must be mounted securely on a solid wall or structure, with the idler motors positioned on a stable, level surface.
Adequate clearance must be provided around the panel and motors for ventilation, wiring access, inspection, and service. The installation area should be dry, protected, and free of obstructions.
Service size, wire size, and breaker sizing must be selected according to the model requirements, input voltage, and load conditions. The installer must follow the wire size chart and breaker recommendations provided in the manual or inside the panel.
All final sizing and overcurrent protection must be verified by a qualified, licensed electrician before energizing the unit.
Installation, service sizing, and breaker selection must be performed by a qualified, licensed electrician. Verify all wiring, grounding, and breaker sizes before startup.
03 — Dual Zone 230 V Series
Connect the incoming single-phase power line to terminals T1 and T2.
Use bolt-down lugs and properly sized wire for the installation. Refer to the wire size chart for the correct wire gauge. The wire size chart is based on a maximum wire run of 50 feet.
It is recommended to keep the single-phase line as short as possible. If the wire run exceeds 50 feet, increase the wire size by one gauge size for every additional 50 feet of distance.
All wiring should be installed in accordance with applicable electrical codes and performed by a qualified electrician.
Verify utility transformer size, service capacity, breaker/fuse rating, and wire size before installation. Undersized supply equipment may cause low voltage, overheating, equipment damage, or failure to start. Installation must be performed by a qualified electrician.
04 — Smaller Units
On smaller units, the incoming single-phase power connects to T1 and T2. Connect the two incoming single-phase power wires to the terminals marked:
On smaller units, connect incoming single-phase power only to T1 and T2.
The L1, L2, L3 terminals are for the three-phase output/load connections only.
For recommended wire and breaker sizes, refer to the wire size chart inside the panel or see Part #3PC60 in this manual.
05 — Panel Layout
This diagram shows the general panel wiring layout for smaller units. Use it as a visual reference together with the detailed wiring instructions in this manual.
Installation must be performed by a qualified, licensed electrician. Disconnect and lock out all power before installation or service.
06 — Installation & Electrical
Wire the first idler motor to the power block on the right.
This is the primary idler motor and will always be the first motor to start when the phase converter is engaged.
Follow the wire size chart on the yellow sticker inside the panel. Wire sizing shown on the chart is based on a wire run of 50 feet or shorter.
Make sure all electrical connections are clean, secure, and properly tightened. Loose connections can cause overheating, voltage issues, nuisance breaker tripping, or equipment damage.
Verify wire size, breaker size, and terminal connections before energizing the unit. Installation must be performed by a qualified, licensed electrician.
07 — Operation
The second idler motor connects to the left power block. Do not energize or engage the second power block unless the second idler motor is connected. Operating the second power block without the motor connected may cause improper operation or equipment damage.
A green disable button is located on the front of the unit. When the green button is pressed, the second idler motor is engaged.
There is normally no reason to disable the generator during operation. The green button may be left in the engaged position during normal use.
Always ensure the second idler motor is connected before engaging the left power block. Failure to do so may result in equipment damage.
08 — Idler Motor Wiring
The idler/generator motor must be wired according to the wiring diagram located inside the motor conduit box or on the motor nameplate. Verify the correct voltage before making connections.
For standard NL and PL models, use the 230 V low-voltage connection. For NH and PH models, use the 460 V high-voltage connection.
Connect 1, 6, 7, 12 together to L1 · 2, 4, 8, 10 to L2 · 3, 5, 9, 11 to L3.
Connect 1 & 7 to L1 · 2 & 8 to L2 · 3 & 9 to L3 · 4, 5, 6 together.
The wiring diagrams shown above are for 230 V idler/generator motor connections only. 460 V motor lead wiring is not shown here and is covered in the separate 460 V high-voltage motor manual.
Use one of the three lug styles below to terminate motor leads. Do not use wire nuts for idler motor wiring connections. All connections must be tight, secure, and enclosed in an approved junction box.
09 — Pre-start
Before testing the phase converter, verify that the panel, conduit, and idler motors are installed correctly and that all wiring connections are complete, secure, and tightened properly. Confirm that the installation area is clear and safe before energizing the unit.
This page is intended as a visual pre-start inspection reference. Walk the install with this checklist before applying power.
Installation and testing must be performed by a qualified, licensed electrician. Disconnect and lock out all power before making wiring changes or servicing the unit.
10 — Installation & Electrical
Use the chart below to determine the recommended service size, breaker size, and wire size for Dual Zone rotary phase converter models. All wiring must be sized and installed by a qualified licensed electrician in accordance with local electrical code.
Use MOTOR LOAD type breakers only. Standard (light-duty) breakers may nuisance-trip due to high starting current.
| Model | Total HP | Qty | Each HP | KVA | Service | Max Ind. | Max Res. | Min Brkr | Max Brkr | 1PH Wire | Idler Wire | Panel Size |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GP5/10L | 10 | 2 | 5 | 9 | 10 | 30 | 15.5 | 10 | 60 | 8 | 10 | 20×12×10 |
| GP7/15L | 15 | 2 | 7.5 | 14 | 15 | 41 | 20.9 | 15 | 60 | 6 | 10 | 20×12×10 |
| GP10/20L | 20 | 2 | 10 | 19 | 15 | 52 | 25.8 | 20 | 100 | 6 | 8 | 20×12×10 |
| GP15/30L | 30 | 2 | 15 | 28.2 | 25 | 80 | 42.7 | 30 | 120 | 4 | 6 | 20×16×8 |
| GP20/40L | 40 | 2 | 20 | 37 | 30 | 104 | 50.2 | 40 | 150 | 4 | 6 | 20×16×8 |
| GP25/50L | 50 | 2 | 25 | 47 | 30 | 126 | 63.1 | 60 | 200 | 2 | 4 | 20×16×8 |
| GP30/60L | 60 | 2 | 30 | 56 | 50 | 160 | 84.5 | 60 | 200 | 3 | 3 | 20×20×8 |
| GP40/80L | 80 | 2 | 40 | 74 | 50 | 206 | 112.5 | 80 | 300 | 1 | 3 | 20×20×8 |
| GP50/100L | 100 | 2 | 50 | 94 | 75 | 250 | 148.9 | 80 | 350 | 1/0 | 2 | 24×24×8 |
| GP60/120L | 120 | 2 | 60 | 112 | 75 | 320 | 160 | 125 | 400 | 3/0 | 1/0 | 20×20×8 × |
| GP75/150L | 150 | 2 | 75 | 140 | 100 | 448 | 225 | 125 | 500 | 4/0 | 1/0 | 24×24×8 ×2 |
Phase converters can draw high starting current. Use MOTOR LOAD type breakers only. Standard breakers may nuisance trip and cause downtime.
Refer to the model wiring diagram for correct wiring of input, output, and idler motor connections.
All electrical work must comply with the National Electrical Code (NEC) and local codes.
11 — Reference
The table below lists common motor-load breaker part numbers used with rotary phase converter installations. These are reference only. Always verify compatibility with your panel, voltage, and application requirements.
| Manufacturer | Breaker series (motor-load) | 1 pole | 2 pole | 3 pole | Notes |
|---|---|---|---|---|---|
| Square D by Schneider Electric | QO™ | QO1xxx | QO2xxx | QO3xxx | Standard QO series; use HACR or motor-rated as required by code. |
| Siemens | QP™ | QP1xxx | QP2xxx | QP3xxx | Type QP circuit breakers; verify interrupt rating and panel listing. |
| Eaton | BR™ | BR115 | BR215 | BR315 | BR Type breakers; suitable for motor-load applications. |
| ABB | THQL® | THQL1115 | THQL2115 | THQL3115 | THQL series; verify panel compatibility and voltage rating. |
| Murray by Eaton | MP™ | MP115 | MP215 | MP315 | MP series; used in Murray / Eaton panelboards. |
| GE | THQL® | THQL1115 | THQL2115 | THQL3115 | GE THQL series; confirm panel type and application. |
Breaker part numbers vary by amp rating, interrupt rating, voltage rating, and pole configuration. Always match the breaker to the service panel manufacturer and panel label. Do not install breakers that are not listed for use in the panel.
All electrical work must comply with the National Electrical Code (NEC) and local codes.
12 — Troubleshooting Layer
Use these decision cards to quickly identify common issues and actions. Always follow safety procedures and the installation manual.
Check disconnect, breaker, input voltage, control power, and start circuit. Check for voltage dropping while trying to start. Never leave the phase converter on for more than 2 seconds if it does not start.
Record breaker size/type, feeder distance, service details, and whether the idler reaches speed.
Confirm meter placement phase-to-phase. Capture no-load and under-load readings.
Separate converter startup from machine startup. Confirm machine voltage and controls.
Explain generated-leg behavior and where to measure. Do not diagnose from one clamp reading.
Send model, order/serial, photos, readings, breaker/service info, and machine nameplate.
Only qualified, licensed electricians should install, service, and troubleshoot this equipment. Disconnect and lock out all power before opening or working on the panel.
13 — FAQ
The DualZone is a precision-balanced rotary phase converter that turns single-phase utility power into three-phase power for shop equipment. The DualZone uses two idler/generator motors so the operator can choose how much capacity to bring online from a single control panel.
Connect the incoming single-phase line to terminals T1 and T2 inside the control panel. Use bolt-down lugs and properly sized wire. Refer to the wire size chart on the yellow sticker inside the panel for the correct gauge.
The primary idler always runs when the converter is engaged. The second idler is enabled by a green button on the front of the panel. The green button can be left engaged during normal use. Do not energize the second power block unless the second idler motor is actually connected.
Use motor-load (HACR or motor-rated) breakers only. Standard light-duty breakers may nuisance-trip on the high inrush of a rotary phase converter. Common compatible series include Square D QO, Siemens QP, Eaton BR, ABB THQL, Murray MP, and GE THQL.
Never leave the converter energized for more than two seconds if it does not start. Disconnect power and troubleshoot the disconnect, breaker, input voltage, control power, and start circuit before retrying.
Installation must be performed by a qualified, licensed electrician in accordance with the National Electrical Code (NEC) and local codes. Disconnect and lock out all power sources before installing or servicing the unit.
The wire size chart in the manual is based on a maximum wire run of 50 feet. Keep the single-phase line as short as possible. If the run exceeds 50 feet, increase the wire size by one gauge for every additional 50 feet.
NL and PL models use the 230 V low-voltage motor connection. NH and PH models use the 460 V high-voltage connection. 460 V motor lead wiring is covered in the separate 460 V high-voltage motor manual.
Need a hand?
If you are sizing a DualZone, retrofitting an existing shop, or working through a startup issue, we will walk it through with you. Bring your machine nameplate, service details, and a photo of your panel.
Enter your email and we’ll unlock the Phoenix Phase Converters manual download.
Talk to a Phase Converter Engineer
📞 (800) 417-6568Free sizing help • Lifetime warranty • Made in USA • Mon–Fri 7AM–5PM MST