How to Size a Phase Converter for Multiple Motors

Most shops run more than one three-phase machine from one converter. You don't add up every motor in the shop. Here's how we size it.

The rule: biggest machine gets its factor, everything else running at the same time adds at 1×

  1. Find the biggest (or first-to-start) machine and size it with its own factor: most machines (lathes, CNC spindles, saws, pumps) × 2, air compressors and dust collectors × 2.5, vacuum pumps × 3, manual mills one size up.
  2. Add the horsepower of every other machine that runs at the same time at 1×.
  3. Round up to the next converter size.

Machines that never run at the same time don't add. One operator running a lathe and a mill, one at a time, only needs the converter sized for the lathe.

Examples

Your shop Math Converter
7.5 HP lathe and 2 HP mill, one operator 7.5 × 2 = 15 (mill not added) GP15NL
10 HP saw + 3 HP drill press + 5 HP dust collector, all running 10 × 2 + 3 + 5 = 28 GP30NL
7.5 HP compressor + 7.5 HP planer 7.5 × 2.5 + 7.5 = 26.25 GP30NL
CNC router: 5 HP vacuum + 10 HP spindle 5 × 3 + 10 = 25 GP25PLA

Air compressors are the exception

A compressor turns itself on whenever tank pressure drops, so it can start while everything else is running. If a compressor shares the converter with a laser cutter or a granite saw, give the compressor its full × 2.5 too: for example, a 10 HP saw and a 5 HP compressor is 10 × 2 + 5 × 2.5 = 32.5, so a 40 HP converter.

Machines that start at the same moment

If several motors start together, for example irrigation pivots after the power comes back, add up the horsepower of the motors that start together and multiply by 2. Then compare it with the total horsepower of everything running, and use whichever is bigger.

Start the biggest machine first

Turn on the converter, then start your biggest machine, then the smaller ones.

Big shops and limited service

If the total comes out over 30 HP, call us. The converter has to be smaller than the kVA of your building's service. When it isn't, a DualZone (two smaller idlers on one control panel that start one after the other) keeps the starting draw down and cuts the wire and breaker size.

Not sure of the horsepower? Text a photo of the motor nameplate to 800-417-6568, or call the same number and we'll size it with you.

Want us to check your sizing?

Call 800-417-6568 with your machine list. Every Phoenix converter comes with a lifetime warranty on the control panel; the idler motor carries a 3-year warranty from the motor maker.

Talk to a Phase Converter Engineer

📞 800-417-6568

Free sizing help • Lifetime warranty • Made in USA • Mon–Fri 7AM–5PM MST

Sunday,Monday,Tuesday,Wednesday,Thursday,Friday,Saturday
January,February,March,April,May,June,July,August,September,October,November,December
Not enough items available. Only [max] left.
Add to WishlistBrowse WishlistRemove Wishlist
Shopping cart

Your cart is empty.

Return To Shop

Add Order Note Edit Order Note
Estimate Shipping
Add A Coupon

Estimate Shipping

Add A Coupon

Coupon code will work on checkout page

Call an Expert
Call Us
Contact Us