Find common single-phase breaker part numbers by panel brand, understand motor-load breaker sizing, and get practical guidance for rotary phase converters, CNC machines, air compressors, dust collectors, pumps, saws, lathes, mills, and other industrial equipment.
A breaker for a motor circuit is not sized like a light switch or regular receptacle circuit. Motors pull high startup current. A rotary phase converter may also require a properly sized input breaker, wire, disconnect, and overload protection based on the actual equipment nameplate and local electrical code.
Use these as starting points for selecting the converter size before final electrical design.
These are common breaker families used in residential and light commercial panels. Always verify the exact panel label before installation.
Common family: QP
Examples: Q120, Q220, Q240
Common family: HOM
Examples: HOM120, HOM220, HOM240
Common family: QO
Examples: QO120, QO220, QO240
Common family: BR
Examples: BR120, BR220, BR240
Common family: CH or CHF
Examples: CH120, CH220, CH240
Common family: THQL
Examples: THQL1120, THQL2120, THQL2140
For 120V single-phase motor loads. Many larger motor and phase converter circuits are 240V and use 2-pole breakers instead.
| Amps | Siemens QP | Square D HOM | Square D QO | Eaton BR | Eaton CH | GE / ABB THQL | Leviton LB |
|---|---|---|---|---|---|---|---|
| 15A | Q115 | HOM115 | QO115 | BR115 | CH115 | THQL1115 | LB115-T |
| 20A | Q120 | HOM120 | QO120 | BR120 | CH120 | THQL1120 | LB120-T |
| 25A | Q125 | HOM125 | QO125 | BR125 | CH125 | THQL1125 | LB125-T |
| 30A | Q130 | HOM130 | QO130 | BR130 | CH130 | THQL1130 | LB130-T |
| 40A | Q140 | HOM140 | QO140 | BR140 | CH140 | THQL1140 | LB140-T |
| 50A | Q150 | HOM150 | QO150 | BR150 | CH150 | THQL1150 | LB150-T |
| 60A | Q160 | HOM160 | QO160 | BR160 | CH160 | THQL1160 | LB160-T |
Use this table for common 240V single-phase motor loads and many rotary phase converter input circuits. The final breaker must match the panel and equipment requirements.
| Amps | Siemens QP | Square D HOM | Square D QO | Eaton BR | Eaton CH | GE / ABB THQL | Leviton LB |
|---|---|---|---|---|---|---|---|
| 15A | Q215 | HOM215 | QO215 | BR215 | CH215 | THQL2115 | LB215-T |
| 20A | Q220 | HOM220 | QO220 | BR220 | CH220 | THQL2120 | LB220-T |
| 25A | Q225 | HOM225 | QO225 | BR225 | CH225 | THQL2125 | LB225-T |
| 30A | Q230 | HOM230 | QO230 | BR230 | CH230 | THQL2130 | LB230-T |
| 40A | Q240 | HOM240 | QO240 | BR240 | CH240 | THQL2140 | LB240-T |
| 50A | Q250 | HOM250 | QO250 | BR250 | CH250 | THQL2150 | LB250-T |
| 60A | Q260 | HOM260 | QO260 | BR260 | CH260 | THQL2160 | LB260-T |
| 70A | Q270 | HOM270 | QO270 | BR270 | CH270 | THQL2170 | LB270-T |
| 80A | Q280 | HOM280 | QO280 | BR280 | CH280 | THQL2180 | LB280-T |
| 90A | Q290 | HOM290 | QO290 | BR290 | CH290 | THQL2190 | LB290-T |
| 100A | Q2100 | HOM2100 | QO2100 | BR2100 | CH2100 | THQL21100 | LB2100-T |
These examples help customers understand why the machine type matters before asking for a quote.
| Equipment Type | Example Motor | Recommended Converter Rule | Example Converter Class | Notes |
|---|---|---|---|---|
| CNC mill, lathe, mill, drill, grinder | 15 HP | 2× HP | 30 HP class | Good fit for many general industrial loads. |
| Air compressor | 20 HP | 2.5× HP | 50 HP class | Compressors pull high starting current. |
| Dust collector or fan | 25 HP | 3× HP | 75 HP class | Fans and dust collectors are heavy-starting loads. |
| 480V machine from 240V single phase | Varies | Converter + transformer | Matched package | A rotary phase converter alone does not step voltage from 240V to 480V. |
Send us your machine HP, voltage, equipment type, and what runs at the same time. Phoenix Phase Converters will help size the rotary phase converter, transformer package, and electrical requirements.
The breaker depends on the converter size, input voltage, wire size, disconnect, and local code. Use the equipment nameplate and installation manual, then have the electrician verify the breaker and conductor size.
No. Use only breakers listed for the exact breaker panel. Breakers from different brands may physically fit but may not be listed or safe for that panel.
No. The breaker is usually short-circuit and ground-fault protection. The motor still needs proper overload protection through a starter, overload relay, VFD, or listed motor protection device.
Most 230/240V single-phase phase converter inputs use a 2-pole breaker. A 1-pole breaker is typically for 120V loads.
Yes, but it usually requires a rotary phase converter plus a step-up transformer. The phase converter creates three-phase power; the transformer changes voltage.