Motor Horsepower | Motor Amperes | Breaker Size | Starter Size | Heater Amperes | Wire Size | Conduit Size | |
---|---|---|---|---|---|---|---|
½ | 230 V 460 V |
2.2 1.1 |
15 15 |
00 00 |
2.53 1.265 |
12 12 |
¾ ¾ |
¾ | 230 V 460 V |
3.2 1.6 |
15 15 |
00 00 |
3.68 1.84 |
12 12 |
¾ ¾ |
1 | 230 V 460 V |
4.2 2.1 |
15 15 |
00 00 |
4.83 2.415 |
12 12 |
¾ ¾ |
1½ | 230 V 460 V |
6 3 |
15 15 |
00 00 |
6.9 3.45 |
12 12 |
¾ ¾ |
2 | 230 V 460 V |
6.8 3.4 |
15 15 |
0 00 |
7.82 3.91 |
12 12 |
¾ ¾ |
3 | 230 V 460 V |
9.6 4.8 |
20 15 |
0 0 |
11.04 5.52 |
12 12 |
¾ ¾ |
5 | 230 V 460 V |
15.2 7.6 |
30 15 |
1 0 |
17.48 8.74 |
12 12 |
¾ ¾ |
7½ | 230 V 460 V |
22 11 |
45 20 |
1 1 |
25.3 12.65 |
10 12 |
¾ ¾ |
10 | 230 V 460 V |
28 14 |
60 30 |
2 1 |
32.2 16.1 |
10 12 |
¾ ¾ |
15 | 230 V 460 V |
42 21 |
70 40 |
2 2 |
48.3 24.15 |
6 10 |
1 ¾ |
20 | 230 V 460 V |
54 27 |
100 50 |
3 2 |
62.1 31.05 |
4 10 |
1 ¾ |
25 | 230 V 460 V |
68 34 |
100 50 |
3 2 |
78.2 39.1 |
4 8 |
1½ 1 |
30 | 230 V 460 V |
80 40 |
125 70 |
3 3 |
92 46 |
3 8 |
1½ 1 |
40 | 230 V 460 V |
104 52 |
175 100 |
4 3 |
119.6 59.8 |
1 6 |
1½ 1 |
50 | 230 V 460 V |
130 65 |
200 150 |
4 3 |
149.5 74.75 |
00 4 |
2 1½ |
60 | 230 V 460 V |
154 77 |
250 200 |
5 4 |
177.1 88.55 |
000 3 |
2 1½ |
75 | 230 V 460 V |
192 96 |
300 200 |
5 4 |
220.8 110.4 |
250kcmil 1 |
2½ 1½ |
100 | 230 V 460 V |
248 124 |
400 200 |
5 4 |
285.2 142.6 |
350kcmil 2/0 |
3 2 |
125 | 230 V 460 V |
312 156 |
500 250 |
6 5 |
358.8 179.4 |
600kcmil 000 |
3½ 2 |
150 | 230 V 460 V |
360 180 |
600 300 |
6 5 |
414 207 |
700kcmil 0000 |
4 2½ |