Full Load Current

Motor Horsepower Motor Amperes Breaker Size Starter Size Heater Amperes Wire Size Conduit Size
½ 230 V
460 V
2.2
1.1
15
15
00
00
2.53
1.265
12
12
¾
¾
¾ 230 V
460 V
3.2
1.6
15
15
00
00
3.68
1.84
12
12
¾
¾
1 230 V
460 V
4.2
2.1
15
15
00
00
4.83
2.415
12
12
¾
¾
230 V
460 V
6
3
15
15
00
00
6.9
3.45
12
12
¾
¾
2 230 V
460 V
6.8
3.4
15
15
0
00
7.82
3.91
12
12
¾
¾
3 230 V
460 V
9.6
4.8
20
15
0
0
11.04
5.52
12
12
¾
¾
5 230 V
460 V
15.2
7.6
30
15
1
0
17.48
8.74
12
12
¾
¾
230 V
460 V
22
11
45
20
1
1
25.3
12.65
10
12
¾
¾
10 230 V
460 V
28
14
60
30
2
1
32.2
16.1
10
12
¾
¾
15 230 V
460 V
42
21
70
40
2
2
48.3
24.15
6
10
1
¾
20 230 V
460 V
54
27
100
50
3
2
62.1
31.05
4
10
1
¾
25 230 V
460 V
68
34
100
50
3
2
78.2
39.1
4
8

1
30 230 V
460 V
80
40
125
70
3
3
92
46
3
8

1
40 230 V
460 V
104
52
175
100
4
3
119.6
59.8
1
6

1
50 230 V
460 V
130
65
200
150
4
3
149.5
74.75
00
4
2
60 230 V
460 V
154
77
250
200
5
4
177.1
88.55
000
3
2
75 230 V
460 V
192
96
300
200
5
4
220.8
110.4
250kcmil
1

100 230 V
460 V
248
124
400
200
5
4
285.2
142.6
350kcmil
2/0
3
2
125 230 V
460 V
312
156
500
250
6
5
358.8
179.4
600kcmil
000

2
150 230 V
460 V
360
180
600
300
6
5
414
207
700kcmil
0000
4

Wire Size Reference — FAQ

Do I use the converter HP or my equipment HP to size the input wire?

Size input wire based on the converter's single-phase input amps — which is approximately 2x the three-phase FLA of your equipment. The converter nameplate lists the input amp rating.

What wire type should I use?

THHN or THWN-2 copper in conduit is standard for phase converter installations. Use EMT or rigid conduit — vibration from the idler motor can damage unprotected wire runs.